Armored / Unarmored Cables For various industrial projects we have brought an extremely wide range of finest quality Armored- Unarmored Cables. These cables are flexible and tested for their finest performance. All standard specifications are stringently followed for making these cables. Our experts are well fledged with the knowledge of industrial components therefore they help in bringing forth finest quality materials for clients. With below given specifications Armored- Unarmored Cables are available. Solid/ Stranded copper/ Aluminum. (For Industrial plant, Infrastructure projects etc.) Electrocab 1.1 KV Annealed High Conductivity Solid Copper Conductor, 1.5 SQ MM PVC Insulated Inner Sheathed, Armoured/ Unarmoured PVC Sheathed Cables Conforming TO IS: 1554(PART-I)
|
Nominal of cores
|
Nominal thickness of insulation sheath
mm
|
Min Thickness of lnner sheath
mm
|
ARMOUR
|
Nominal Sheath Thickness Unarmoured
mm
|
Minimum Sheath Thickness Armoured
mm
|
Approx Overall Diameter
|
Approx Weight of Cable
|
Max.DC Conductor Resistance at 20C
Ohm/Km
|
CURRENT RATINGS
|
|
Galv Round Steel Wire Nom dia
mm
|
Galv Flat Steel Strip Nom thick
mm
|
Unarmoured
mm
|
Armoured
mm
|
Unarmoured
mm
|
Armoured
mm
|
Direct in Ground
Amps
|
In Ducts
Amps
|
In Air
Amps
|
|
2
|
0.8
|
0.3
|
1.4
|
-
|
1.80
|
1.24
|
11.5
|
14.0
|
130
|
350
|
12.1
|
23
|
20
|
20
|
|
3
|
0.8
|
0.3
|
1.4
|
-
|
1.80
|
1.24
|
12.0
|
14.5
|
160
|
400
|
12.1
|
21
|
17
|
17
|
|
4
|
0.8
|
0.3
|
1.4
|
-
|
1.80
|
1.24
|
13.0
|
15.0
|
190
|
450
|
12.1
|
21
|
17
|
17
|
|
5
|
0.8
|
0.3
|
1.4
|
-
|
1.80
|
1.24
|
14.0
|
16.0
|
225
|
500
|
12.1
|
21
|
17
|
17
|
|
6
|
0.8
|
0.3
|
1.4
|
-
|
1.80
|
1.24
|
15.0
|
17.0
|
250
|
550
|
12.1
|
15
|
13
|
13
|
|
7
|
0.8
|
0.3
|
1.4
|
-
|
1.80
|
1.24
|
15.0
|
17.0
|
265
|
565
|
12.1
|
14
|
13
|
13
|
|
10
|
0.8
|
0.3
|
1.4
|
-
|
1.80
|
1.24
|
18.0
|
20.5
|
350
|
620
|
12.1
|
13
|
11
|
10
|
|
12
|
0.8
|
0.3
|
-
|
0.8
|
1.80
|
1.40
|
18.5
|
19.5
|
400
|
700
|
12.1
|
12
|
10
|
10
|
|
14
|
0.8
|
0.3
|
-
|
0.8
|
1.80
|
1.40
|
19.5
|
20.5
|
450
|
760
|
12.1
|
11
|
10
|
10
|
|
16
|
0.8
|
0.3
|
-
|
0.8
|
1.80
|
1.40
|
20.5
|
21.5
|
500
|
800
|
12.1
|
11
|
9
|
9
|
|
19
|
0.8
|
0.3
|
-
|
0.8
|
2.00
|
1.40
|
22.0
|
22.5
|
600
|
850
|
12.1
|
10
|
9
|
9
|
|
24
|
0.8
|
0.3
|
-
|
0.8
|
2.00
|
1.40
|
25.0
|
25.5
|
725
|
1050
|
12.1
|
9
|
8
|
8
|
|
30
|
0.8
|
0.3
|
-
|
0.8
|
2.00
|
1.40
|
26.5
|
27.5
|
860
|
1200
|
12.1
|
9
|
7
|
7
|
|
37
|
0.8
|
0.3
|
-
|
0.8
|
2.00
|
1.40
|
28.0
|
28.5
|
1050
|
1400
|
12.1
|
8
|
7
|
7
|
|
61
|
0.8
|
0.4
|
-
|
0.8
|
2.20
|
1.56
|
35.0
|
36.5
|
1650
|
2100
|
12.1
|
7
|
6
|
6
|
Electrocab 1.1 KV Annealed High Conductivity Solid Copper Conductor, 2.5 SQ MM PVC Insulated Inner Sheathed, Armoured/ Unarmoured PVC Sheathed Cables Conforming TO IS: 1554(PART-I)
|
Nominal of cores
|
Nominal thickness of insulation sheath
mm
|
Min Thickness of lnner sheath
mm
|
ARMOUR
|
Nominal Sheath Thickness Unarmoured
mm
|
Minimum Sheath Thickness Armoured
mm
|
Approx Overall Diameter
|
Approx Weight of Cable
|
Max.DC Conductor Resistance at 20C
Ohm/Km
|
CURRENT RATINGS
|
|
Galv Round Steel Wire Nom dia
mm
|
Galv Flat Steel Strip Nom thick
mm
|
Unarmoured
mm
|
Armoured
mm
|
Unarmoured
mm
|
Armoured
mm
|
Direct in Ground
Amps
|
In Ducts
Amps
|
In Air
Amps
|
|
2
|
0.9
|
0.3
|
1.4
|
-
|
1.8
|
1.24
|
13.0
|
15.0
|
160
|
425
|
7.41
|
32
|
27
|
27
|
|
3
|
0.9
|
0.3
|
1.4
|
-
|
1.8
|
1.24
|
14.0
|
16.0
|
225
|
475
|
7.41
|
27
|
24
|
24
|
|
4
|
0.9
|
0.3
|
1.4
|
-
|
1.8
|
1.24
|
14.5
|
17.0
|
250
|
530
|
7.41
|
27
|
24
|
24
|
|
5
|
0.9
|
0.3
|
1.4
|
-
|
1.8
|
1.24
|
15.5
|
18.0
|
300
|
600
|
7.41
|
27
|
24
|
24
|
|
6
|
0.9
|
0.3
|
1.4
|
-
|
1.8
|
1.24
|
17.0
|
19.0
|
340
|
675
|
7.41
|
20
|
18
|
18
|
|
7
|
0.9
|
0.3
|
1.4
|
-
|
1.8
|
1.24
|
17.0
|
19.0
|
375
|
700
|
7.41
|
20
|
17
|
17
|
|
10
|
0.9
|
0.3
|
-
|
0.8
|
1.8
|
1.40
|
20.5
|
22.0
|
500
|
780
|
7.41
|
18
|
15
|
15
|
|
12
|
0.9
|
0.3
|
-
|
0.8
|
2.0
|
1.40
|
21.0
|
22.5
|
600
|
850
|
7.41
|
17
|
14
|
14
|
|
14
|
0.9
|
0.3
|
-
|
0.8
|
2.0
|
1.40
|
22.5
|
23.5
|
650
|
950
|
7.41
|
16
|
13
|
13
|
|
16
|
0.9
|
0.3
|
-
|
0.8
|
2.0
|
1.40
|
23.5
|
24.5
|
750
|
1050
|
7.41
|
15
|
13
|
13
|
|
19
|
0.9
|
0.3
|
-
|
0.8
|
2.0
|
1.40
|
24.5
|
25.5
|
850
|
1150
|
7.41
|
14
|
12
|
12
|
|
24
|
0.9
|
0.3
|
-
|
0.8
|
2.0
|
1.40
|
28.5
|
29.5
|
1050
|
1400
|
7.41
|
13
|
11
|
11
|
|
30
|
0.9
|
0.3
|
-
|
0.8
|
2.0
|
1.56
|
30.5
|
31.0
|
1250
|
1700
|
7.41
|
12
|
10
|
10
|
|
37
|
0.9
|
0.4
|
-
|
0.8
|
2.2
|
1.56
|
32.5
|
33.5
|
1550
|
2000
|
7.41
|
11
|
10
|
10
|
|
61
|
0.9
|
0.4
|
-
|
0.8
|
2.2
|
1.56
|
40.5
|
41.5
|
2450
|
3100
|
7.41
|
9
|
8
|
8
|
Current Ratings of Electrocab Copper Armoured/Unarmoured Cables 650/110 V Grade in Air
|
Area Sq mm
|
Twin Core Amp
|
3,3 1/ 2, 4 Core Amp
|
Area Sq mm
|
Twin Core Amp
|
3,3 1/ 2, 4 Core Amp
|
|
1.5
|
20
|
17
|
70
|
195
|
165
|
|
2.5
|
27
|
24
|
95
|
230
|
200
|
|
4.0
|
35
|
30
|
120
|
265
|
235
|
|
6.0
|
45
|
39
|
150
|
305
|
265
|
|
10
|
60
|
52
|
185
|
350
|
305
|
|
16
|
78
|
66
|
240
|
410
|
355
|
|
25
|
105
|
90
|
300
|
465
|
400
|
|
35
|
125
|
110
|
400
|
530
|
455
|
|
50
|
155
|
135
|
|
|
|
|